108kVA 27kV 100kV Series High Voltage Resonant Test System Portable Type

Ask Latest Price
Video Channel
Brand Name :Ningbo Suntech Power
Model Number :FKTF-108kVA/27kV;100kV
Certification :ISO9001
Place of Origin :Ningbo,China
MOQ :One Unit
Price :Negotiable
Payment Terms :T/T
Supply Ability :10units/1months
Delivery Time :25-30 Work Days
Packaging Details :Export Standard Wooden Case With Fumigation Free
Test Principle :Variable Frequency Resonant Circuit
Rated Capacity :108kVA
Design Feature :Portable Type
Test Frequency :30-300Hz
Duty Cycle :15min
Test Standard :IEC 60060-1:2010;IEC 62271-203:2011 For GIS, IEC 60840:2011 For XLPE Cable;
Rated Voltage :27kV;100kV
High Light :100kV Series Resonant Test System, 27kV Resonant Test System, 108kVA AC Resonant Test System
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Series resonance test device

1. Subject
1.10kV/300mm2 cable, unit length capacitance 0.37uF/km, cable length 1.4km, tested cable capacitance 0.153uF, test frequency 30-300Hz, test voltage 52kV, withstand voltage time 60min;
2. 35kV power transformer power frequency AC withstand voltage test, capacitance ≤0.02uF, test frequency 45~65Hz, test voltage not exceeding 68kV, test time 1min;
3. AC withstand voltage test for switches and transformers with voltage levels of 35kV and below, the test frequency is 30-300Hz, the test voltage does not exceed 100kV, and the test time is 1min;
2. Environmental conditions for device use
1. Ambient temperature: -5℃—45℃;
2. Relative humidity: ≤90﹪, no condensation;
3. Altitude: ≤1000m.
3. The main technical parameters and functions of the system
1. Rated capacity: 108kVA;
2. Rated voltage: 27kV; 100kV;
3. Rated current: 4A; 1A;
4. Power supply: single-phase 220V±10﹪;
5. Working frequency: 30-300Hz;
6. Frequency resolution: 0.1Hz; frequency instability: ≤0.1%;
7. Working time: 15min continuous operation is allowed under rated power;
8. Temperature rise: After 15 minutes of continuous operation at rated power, the temperature rise of each part of the device is ≤65K;
9. Output waveform: sine wave, waveform distortion rate <1%;
10. Quality factor: the device itself Q≥30 (when f=45Hz);
11. Protection: with over-current, over-voltage and flashover protection (see the frequency conversion power supply section for auspiciousness);
12. System measurement accuracy: effective value 1.5.

Configuration equipment list

number Equipment name Models and Specifications unit Quantity
Frequency Power FKVF-6kW/220V station 1
Excitation transformer CQSB(J)-6kVA/1.5×4kV/0.225kV station 1
Dry reactor CHX(Jf)-27kVA/27kV Section 4
Capacitor voltage divider TRF-100kV/150pF station 1
Compensation capacitor BWF-100kV/14.5nf station 1
Insulation support set 1
Equalizing ring set 1
Wiring set 1
Inquiry Cart 0